Print Back
Unit of Measure

Technical Specs

Brands

N/A Mydax, Inc.

Temperature Range

N/A -60 to +35 ºC

Environment

N/A Outdoor

BTU/hr

N/A Varies

kW

N/A Varies

Tons

N/A Varies

Product Type

N/A Unit - Cryo

Description/Required Options

N/A Required Option A, B, G & H

Stability

N/A ±1.0 ºC

Heating Capacity

N/A 3,000 Watts on 460 VAC

Recirculating Supply

N/A 2 in. Stainless Steel Female National Pipe Thread (FNPT)

Facilities Supply

N/A 1 in. Stainless Steel Female National Pipe Tapered (FNPT) in

Condenser Requirements

N/A 20 psi ΔP, Supply-to-drain Up to 20 gpm at 70 ºF inlet Up to 23 gpm at 85 ºF inlet

Alternating Current (AC) Voltage

N/A 380/420 V440/480 V

Frequency at 440/480 Volt (V) Voltage

N/A 60 Hz

Frequency at 380/420 Volt (V) Voltage

N/A 50 Hz

Phase at 440/480 Volt (V) Voltage

N/A 3

Phase at 380/420 Volt (V) Voltage

N/A 3

Current at 440/480 Volt (V) Voltage

N/A 80 A

Current at 380/420 Volt (V) Voltage

N/A 80 A

Recirculation

N/A 3.0 Hp SS Seal-Less canned motor centrifugal pump, SS turbine flow meter, Output flow adjust valve, panel mounted pressure gauge, copper piping

Recirculating Flow/Pressure

N/A 30 gpm at 35 psi

Stainless Steel Reservoir

N/A 125 gallons (Sealable with nitrogen blanket provisions)

Recirculating Fluid

N/A Syltherm HF/XLT or equivalent

Facilities Requirements

N/A Up to 21 gpm at 70 ºF inlet, 20 psi ΔP

Maximum Heat Rejection

N/A 259,000 Btu/hr

Approximate Dry Weight

N/A 2200 lb

Warranty (Parts and Labor)

N/A 12 months

Patents

N/A #4,742,689 #4,934,155 #4,959,972

Refrigeration

N/A Two 20 Hp semi-hermetically sealed, two-stage compressors in a parallel configuration, R448A refrigerant

System Dimensions

Height

N/A 74 in

Width

N/A 60 in

Depth

N/A 65 in