Unit of Measure
Technical Specs
Brands |
N/A Mydax, Inc. |
Temperature Range |
N/A -60 to +35 ºC |
Environment |
N/A Outdoor |
BTU/hr |
N/A Varies |
kW |
N/A Varies |
Tons |
N/A Varies |
Product Type |
N/A Unit - Cryo |
Description / Required Options |
N/A Required Option A, B, G & H |
Stability |
N/A ±1.0 ºC at Temperatures Below -30 ºC |
Heating Capacity |
N/A 3,000 W |
Recirculating Flow/Pressure |
N/A 30 gpm at 35 psi |
Stainless Steel Reservoir |
N/A 250 gallons (Sealable with nitrogen blanket provisions) |
Recirculating Fluid |
N/A Syltherm HF/XLT or equivalent |
Recirculating Supply |
N/A 2 in. Stainless Steel Female National Pipe Tapered (FNPT) |
Facilities Supply |
N/A 1-1/2 in. Stainless Steel Female National Pipe Tapered (FNPT) in |
Facilities Requirements |
N/A Up to 57 gpm at 70 ºF inlet, 20 psi ΔP |
Maximum Heat Rejection |
N/A 700,000 Btu/hr |
Condenser Requirements |
N/A 20 psi ΔP, Supply-to-drain Up to 42 gpm at 70 ºF inlet Up to 50 gpm at 85 ºF inlet |
Alternating Current (AC) Voltage |
N/A 380/420 V440/480 V |
Frequency at 440/480 Voltage |
N/A 60 Hz |
Frequency at 380/420 Voltage |
N/A 50 Hz |
Phase at 440/480 Voltage |
N/A 3 |
Phase at 380/420 Voltage |
N/A 3 |
Current at 440/480 Voltage |
N/A 250 A |
Current at 380/420 Voltage |
N/A 250 A |
Approximate Dry Weight |
N/A 3500 lb |
Warranty (Parts and Labor) |
N/A 12 months |
Patents |
N/A 4,742,689 4,934,155 4,959,972 |
Refrigeration |
N/A Four 30 Hp semi-hermetically sealed, two-stage compressors in a parallel configuration, R448A refrigerant |
Recirculation |
N/A 3.0 Hp SS Seal-Less Mag-Drive Centrifugal pump powered by a VFD, SS turbine flow meter, Bypass flow adjust valve, panel mounted pressure gauge, copper piping |