Catalog

Unit of Measure

Technical Specs

Brands

N/A Mydax, Inc.

Temperature Range

N/A -60 to +80 ºC

Environment

N/A Outdoor

BTU/hr

N/A Varies

kW

N/A Varies

Tons

N/A Varies

Product Type

N/A Unit - Cryo

Description / Required Options

N/A Required Option A, B, G & H

Stability

N/A ±1.0 ºC at Temperatures Below -30 ºC

Heating Capacity

N/A 3,000 W

Recirculating Flow/Pressure

N/A 30 gpm at 35 psi

Stainless Steel Reservoir

N/A 125 gallons (Sealable with nitrogen blanket)

Recirculating Fluid

N/A Dynalene HC-50, Syltherm XLT or Equivalent

Recirculating Supply

N/A 1-1/4 in. Stainless Steel Female National Pipe Tapered (FNPT)

Facilities Supply

N/A 1-1/2 in. Stainless Steel Female National Pipe Tapered (FNPT) in

Facilities Requirements

N/A Up to 57 gpm at 70 ºF inlet, 20 psi ΔP

Maximum Heat Rejection

N/A 700,000 Btu/hr

Alternating Current (AC) Voltage

N/A 380/420 V440/480 V

Frequency at 440/480 Voltage

N/A 60 Hz

Frequency at 380/420 Voltage

N/A 50 Hz

Phase at 440/480 Voltage

N/A 3

Phase at 380/420 Voltage

N/A 3

Current at 440/480 Voltage

N/A 240 A

Current at 380/420 Voltage

N/A 240 A

Approximate Dry Weight

N/A 3300 lb

Warranty (Parts and Labor)

N/A 12 months

Patents

N/A 4,742,689 4,934,155 4,959,972

Refrigeration

N/A Four 30 Hp semi-hermetically sealed compressors, R448A refrigerant

Recirculation

N/A 3.0 Hp SS seal-less magnetic-drive centrifugal pump, turbine fluid flowmeter in recirculating return, pressure gauge, overpressure switch, brazed plate heat exchanger, copper piping

System Dimensions

Height

N/A 74 in

Width

N/A 60 in

Depth

N/A 105 in