Catalog

Unit of Measure

Technical Specs

Brands

N/A Mydax, Inc.

Temperature Range

N/A -70 to +80 ºC

Environment

N/A Indoor

BTU/hr

N/A Varies

kW

N/A Varies

Tons

N/A Varies

Product Type

N/A Unit - Cryo

Description / Required Options

N/A Required Option A

Stability

N/A ±1.0 ºC at Temperatures Below -30 ºC

Heating Capacity

N/A 3,000 W

Recirculating Flow/Pressure

N/A 6 gpm at 40 psi

Stainless Steel Reservoir

N/A 5 gallons (Sealable)

Recirculating Fluid

N/A Syltherm HF or XLT

Recirculating Supply

N/A 3/4 in. Stainless Steel Female National Pipe Tapered (FNPT)

Facilities Supply

N/A 3/4 in. Stainless Steel Female National Pipe Tapered (FNPT) in

Facilities Requirements

N/A Up to 7 gpm at 70 ºF inlet, 20 psi ΔP

Maximum Heat Rejection

N/A 79,000 Btu/hr

Alternating Current (AC) Voltage

N/A 380/420 V440/480 V

Frequency at 440/480 Voltage

N/A 60 Hz

Frequency at 380/420 Voltage

N/A 50 Hz

Phase at 440/480 Voltage

N/A 3

Phase at 380/420 Voltage

N/A 3

Current at 440/480 Voltage

N/A 30 A

Current at 380/420 Voltage

N/A 30 A

Approximate Dry Weight

N/A 980 lb

Warranty (Parts and Labor)

N/A 12 months

Patents

N/A 4,742,689 4,934,155 4,959,972

Refrigeration

N/A 12 Hp semi-hermetically sealed compressor, R448A refrigerant

Recirculation

N/A 1.5 Hp SS seal-less magnetic-drive turbine pump, turbine fluid flowmeter in recirculating return

System Dimensions

Height

N/A 66 in

Width

N/A 36 in

Depth

N/A 56 in