Catalog

Unit of Measure

Technical Specs

Brands

N/A Mydax, Inc.

Temperature Range

N/A -30 to +60 ºC

Environment

N/A Outdoor

BTU/hr

N/A 30,000

kW

N/A 9 kW at -15 ºC (Total is shared between 3 loops Ambient range -20 ºC to +43 ºC)

Tons

N/A 2.50

Product Type

N/A Unit - Air

Stability

N/A ±0.5 ºC

Heating Capacity

N/A 3 kW Each Loop

Recirculating Flow/Pressure

N/A 5 gpm at 110 psi each loop

Stainless Steel Reservoir

N/A 5 gallons (Vented)

Recirculating Fluid

N/A PAO

Recirculating Supply

N/A 3/4 in. Stainless Steel Female National Pipe Tapered (FNPT)

Facilities Supply

N/A 3/4 in. Stainless Steel Female National Pipe Tapered (FNPT) in

Condenser Requirements

N/A 12,400 cfm Directed Upward

Alternating Current (AC) Voltage

N/A 440/480 V

Frequency

N/A 60 Hz

Phase

N/A 3

Current

N/A 70 A

Approximate Dry Weight

N/A 1650 lb

Warranty (Parts and Labor)

N/A 12 months

Patents

N/A 4,742,689 4,934,155 4,959,972

Refrigeration

N/A 20 Hp hermetically sealed compressor, R448A refrigerant, dual fan overhead condenser

Recirculation

N/A Three 1.5 Hp gear pumps powered by VFD’s, rotary flowmeter in recirculating return, panel mounted pressure gauges, Output Check Valve, Return Solenoid, copper piping.

System Dimensions

Height

N/A 81 in

Width

N/A 50 in

Depth

N/A 80 in