Catalog

Unit of Measure

Technical Specs

Brands

N/A Mydax, Inc.

Temperature Range

N/A 0 to +25 ºC

Environment

N/A Outdoor

BTU/hr

N/A 50,000

kW

N/A 14.6 kW at +16 ºC

Tons

N/A 4.10

Product Type

N/A Unit - Air

Stability

N/A ±1.0 ºC

Heating Capacity

N/A 12 kW

Recirculating Flow/Pressure

N/A 85 gpm at 29 psi

Stainless Steel Reservoir

N/A 60 gallons (Vented)

Recirculating Fluid

N/A 50% Ethylene Glycol/50% Water

Recirculating Supply

N/A 2 in. Stainless Steel Female National Pipe Tapered (FNPT)

Facilities Supply

N/A 2 in. Stainless Steel Female National Pipe Tapered (FNPT) in

Maximum Heat Rejection

N/A 94,550 Btu/hr

Condenser Requirements

N/A 6,450 cfm Directed Upward

Alternating Current (AC) Voltage

N/A 440/480 V

Frequency

N/A 60 Hz

Phase

N/A 3

Current

N/A 45 A

Approximate Dry Weight

N/A 1550 lb

Warranty (Parts and Labor)

N/A 12 months

Patents

N/A 4,742,689 4,934,155 4,959,972

Refrigeration

N/A 6 Hp semi-hermetically sealed compressor, R-448A refrigerant, Single overhead fan condenser

Recirculation

N/A 5 Hp SS Centrifugal pump, fluid flowmeter in recirculating return, SS brazed plate heat exchan ger output flow adjust valve, output pressure gauge, over pressure switch, copper piping.

System Dimensions

Height

N/A 81 in

Width

N/A 48 in

Depth

N/A 60 in