Catalog

Unit of Measure

Technical Specs

Brands

N/A Mydax, Inc.

Temperature Range

N/A 5 to +40 ºC

Environment

N/A Indoor

BTU/hr

N/A 27,000

kW

N/A 8,000 Watts at +15 ºC

Tons

N/A 2.25

Product Type

N/A Unit - Water

Stability

N/A ±1.0 ºC

Heating Capacity

N/A 3,000 W

Recirculating Flow/Pressure

N/A 4 gpm at 100 psi Adjustable

Stainless Steel Reservoir

N/A 5 gallons (Vented)

Recirculating Fluid

N/A PAO (MIL-PRF-87252C/Royco 602)

Recirculating Supply

N/A 3/4 in. Stainless Steel Female National Pipe Tapered (FNPT)

Facilities Supply

N/A 3/4 in. Stainless Steel Female National Pipe Tapered (FNPT) in

Condenser Requirements

N/A Up to 6 gpm at 70 ºF inlet

Alternating Current (AC) Voltage

N/A 208/240 V

Frequency

N/A 60 Hz

Phase

N/A 3

Current

N/A 50 A

Approximate Dry Weight

N/A 725 lb

Warranty (Parts and Labor)

N/A 12 months

Patents

N/A 4,742,689 4,934,155 4,959,972

Refrigeration

N/A 7 Hp hermetically sealed scroll compressor, R-507 refrigerant

Recirculation

N/A 2 Hp canned motor SS turbine pump, fluid flowmeter in recirculating return, SS brazed plate heat exchanger, bypass flow adjust valve, output pressure gauge, over pressure switch, copper piping.

System Dimensions

Height

N/A 66 in

Width

N/A 30 in

Depth

N/A 30 in