Catalog

Unit of Measure

Technical Specs

Brands

N/A Mydax, Inc.

Temperature Range

N/A +25 to +50 ºC

Environment

N/A Indoor

BTU/hr

N/A 82,000

kW

N/A 24

Tons

N/A 6.83

Product Type

N/A Heat Exchanger

Stability

N/A ±0.5 ºC

Recirculating Flow/Pressure

N/A 11 gpm at 60 psi

Stainless Steel Reservoir

N/A 4 gallons

Recirculating Fluid

N/A Koolance 702

Recirculating Supply

N/A 3/4 in. Stainless Steel Female National Pipe Thread (FNPT)

Facilities Supply

N/A 3/4 in. Stainless Steel Female National Pipe Tapered (FNPT) in

Facilities Requirements

N/A Up to 10 gpm, 30 psi ΔP

Alternating Current (AC) Voltage

N/A 380 to 480 V

Frequency

N/A 50 Hz60 Hz

Phase

N/A 3

Current

N/A 8 A

Approximate Dry Weight

N/A 150 lb

Warranty (Parts and Labor)

N/A 12 months

Patents

N/A #4,742,689 #4,934,155 #4,959,972

Recirculation

N/A VFD powered 3 Hp SS canned-motor turbine pump, rotary fluid flowmeter, output flow pressure transducer, fixed bypass w/solenoid valve for purging, Nickel-brazed plate heat exchanger, Auto-Fill and Vent Solenoids, copper piping

System Dimensions

Height

N/A 29.5 in

Width

N/A 9.75 in

Depth

N/A 36.5 in